loader image
SS5 Fail Freeze Type Positioner gallery image 1
SS5 Fail Freeze Type Positioner gallery image 1

SS5 Fail Freeze Type Positioner

- Output position transmitter (4 - 20 mA)

- 2 x alarm limit or micro switch (SPDT)

- Explosion proof type (Exia IIC T6) (in progres)

- HART communication

- Profibus PA communication

- Fieldbus FF communication(pending)

Input Signal

4 - 20 mA @ 24 VDC

Min. / Max. Current

3.6 mA / 50mA

Voltage Drop (Resistance)

Without Hart : 8.7 VDC (435Ω @ 20mA)With Hart : 9.4 VDC (470Ω @ 20mA)

Stroke / Angle

Linear type : 8 - 130mm *Rotary type : 25 - 120°

Air Supply Pressure

1.4 - 7.0 bar (20 - 100 psi)

Output Pressure Range

0 - 100% of supply air pressure

Air Capacity

80 l/min = 4.8 Nm3/h = 2.8 scfm (Sup = 1.4 bar)

233 l/min = 14 Nm3/h = 8.2 scfm (Sup = 6 bar)

Air Consumption

2.8 l/min = 0.17 Nm3/h = 0.1 scfm (Sup = 1.4 ~ 6 bar)

Performance Characteristic

Linearity  <  ±0.3% F.S

Sensitivity  <   0.2% F.S

Hysteresis  <   0.2% F.S

              Repeatability  <   0.2% F.S        

LCD Indication

4-digit LCD indicator

Adjustable Speed

1 - 1000 ( lowest 1, highest 1000 )

Scan Time

2ms

Fail freeze level

Input signal < 3mA

Fail freeze drift rate

+2% setpoint / hour at constant temp

Shut-off Value

Range 0 - 10% of position signal

Valve Action

Direct action(DA) / reverse action(RA)

Operating Temperature

-30 ~ +80? (-22 ~ +176?) **

Pneumatic Connections

Rc 1/4 or 1/4 NPT

Electrical Connections

2 x G 1/2 or 1/2 NPT

Protection Class

IP66,  intrinsic safety (Exia IIC T6)

Body Material

Aluminum die-cast / powder-painted

Weight

2 kg

SS5 Series Fail Freeze Type Positioners are positioners that protect the position of the valve in case of failure. The "Fail Freeze" function ensures that the control valve stays in the last position when the electrical power is cut off and informs the position status.