loader image
MK-FK DR Series Coax Solenoid Valve gallery image 1
MK-FK DR Series Coax Solenoid Valve gallery image 1

MK-FK DR Series Coax Solenoid Valve

Order

Orifice

Threaded

Flange

Pressure

Kv

Fluid

Ambient

Temperature

Open Close [ms]

No

[mm]

Connection Size

Connection Size

[bar]

Value

Temperature

A > B

MK 10 DR

DN 10

G 1/4 - G 3/4

-

0 - 16 / 25 / 40

2,6 m³ /h

-20 °C ... +120 °C

-10 °C ... +80 °C

40 / 25

MK / FK 15 DR

DN 15

G 3/8 - G 3/4

PN 16 / 40

0 - 16 / 40

4,3 m³ /h

-20 °C ... +160 °C

-20 °C ... +80 °C

80 / 80

MK / FK 20 DR

DN 20

G 4/4 - G 1 1/4

PN 16 / 40

0 - 16 / 40

6,7 m³ / h

-20 °C ... +160 °C

-20 °C ... +80 °C

110 / 110

MK / FK 25 DR

DN 25

G A - G 1 1/2

PN 16 / 40

0 - 16 / 40

11,2 m³ /h

-20 °C ... +160 °C

-20 °C ... +80 °C

130 / 130

MK / FK 32 DR

DN 32

G 1 1/4 - G 1 1/2

PN 16 / 40

0 - 16 / 40

14,1 m³ / h

-20 °C ... +160 °C

-20 °C ... +80 °C

440 / 250

MK / FK 40 DR

DN 40

G 1/2 - G 2

PN 16

0 - 16

18,4 m³ / h

-20 °C ... +160 °C

-20 °C ... +80 °C

520 / 150

MK / FK 50 DR

DN 50

G 2

PN 16

0 - 16

28,2 m³ / h

-20 °C ... +120 °C

-20 °C ... +80 °C

400 / 400

FK 65 DR

DN 65

-

PN 16

0 - 16

45,0 m³ / h

-20 °C ... +80 °C

-20 °C ... +80 °C

600 / 800

FK 80 DR

DN 80

-

PN 16

0 - 16

55,0 m³ / h

-20 °C ... +80 °C

-20 °C ... +80 °C

600 / 800

Operation : Pressure Balanced spring return

Explosion Proof Class : DIN DVGW acc to DIN 3394 Part 1 DVGW-Ex - G 260/1

Position : NC - normally closed

Body material : Nickel-plated steel

Sealing element : PTFE, FPM

Working pressure : PN 0 - 40 bar

Fluid : Gas, Fluid, G260

Operating voltage : 24 V DC / AC 230 V

Electrical connection : Plug acc to DIN EN 175301-803 Form A, LED M16 x 1.5 Terminal box

Wire Isolation : H 180 ° C

Protection Class : IP 65

Time Spent on Energy : ED 100%

Flow Direction : A> B <B

Optionals : Limit switch, manual control, exproof